Greetings 'Netters,
I have a client with the following situation:
Soltec Maxi Wave
Model: 6523CC
Serial Number: 9603384801
Software: Soltec Communication Module, IBM/XT, Simatic PLC : SMATIC S5-100U
CPU 103
Software .exe: 652XCC
Problem: Zone 1 preheat does not turn on. Indicator light on output module
never comes on. Swapped output modules with no change (old module worked in
new slot). Verified thermocouple is working. Jumpered zone 2 control to zone
1 and got increase in zone 1 temperature, which verified element, wiring,
relay and thermocouple.
I believe the PLC code may have become corrupt and Soltec no longer supports
this version.
Any assistance or suggestions will be appreciated!
Regards,
Ed Popielarski
QTA Machine
27291 Jardines
Mission Viejo, Ca 92692
Ph: 949-581-6601
WWW.QTA.NET
"Keep thine eye on the tach and thine ear on the engine lest the whirlybits
seek communion with the sun"
-Unknown-
---------------------------------------------------
Technet Mail List provided as a service by IPC using LISTSERV 1.8e
To unsubscribe, send a message to [log in to unmask] with following text in
the BODY (NOT the subject field): SIGNOFF Technet
To temporarily halt or (re-start) delivery of Technet send e-mail to [log in to unmask]: SET Technet NOMAIL or (MAIL)
To receive ONE mailing per day of all the posts: send e-mail to [log in to unmask]: SET Technet Digest
Search the archives of previous posts at: http://listserv.ipc.org/archives
Please visit IPC web site http://www.ipc.org/contentpage.asp?Pageid=4.3.16 for additional information, or contact Keach Sasamori at [log in to unmask] or 847-615-7100 ext.2815
-----------------------------------------------------
|
|
|