Howard,

        Test the tile before destroying.  We have learned some flooring will
work as ESD flooring, although it's not marketed as such.

        If you must install something, I would suggest an epoxy slurry floor
coating.  The material is applied at 0.090" thick.  Can be applied over
nearly ANYTHING.  It fills cracks and small voids.  They can add the
appropriate fixtures for grounding, as needed.

        The finished product is durable enough for fork lift traffic.  The
surface is non-slip, even wet.  Installation was done over a weekend and it
took 4 days to fully cure.

        Cost was around $2/sq. ft.

        I believe it was a 3M product, it was several years ago.


Richard Elensky
Sr. Manufacturing Engineer
[log in to unmask] <mailto:[log in to unmask]>

Tel:  559-292-1111  x246
Fax:  559-292-9355

Dantel
2991 North Argyle Ave.
Fresno, CA, 93727
Visit our web site at:
http:// www.dantel.com <http://www.dantel.com>


        ----------
        From:  Howard Watson [SMTP:[log in to unmask]]
        Sent:  Wednesday, October 10, 2001 7:55 AM
        To:  [log in to unmask]
        Subject:  [TN] ESD flooring ideas.


        Dear TechNetters,

        Our PCB assembly area is being consolidated to another building, and
I have the opportunity to request some type of ESD floor coating over an
existing non-ESD tile flooring.  What are your opinions on the best, most
reliable, and of course cheapest, method of ESD flooring?  I am thinking
that removing the existing tile would not be a cost effective alternative.
We are moving out of a facility that had no ESD flooring, so improvements
should be easy to achieve.  Thanks for the assistance.

        Best regards,

        Howard Watson
        Manufacturing Engineer
        AMETEK/Dixson

---------------------------------------------------------------------------------
Technet Mail List provided as a free service by IPC using LISTSERV 1.8d
To unsubscribe, send a message to [log in to unmask] with following text in
the BODY (NOT the subject field): SIGNOFF Technet
To temporarily halt delivery of Technet send the following message: SET Technet NOMAIL